EvoControl Ventilation Touch Display
Models: A100 G3, A110T G3-G4, A170T G2, A200S, A230T, A250S, A390T, A400S, A590T, A600S/T, A900ST G3, A1, A2, M1, M2, R20, R25, R40, R50, R70
| Id | Measurement values | Unit |
|---|---|---|
| 1100 | Drift mode | Off / Stop / Save / Comfort / Boost / Extra 1 / Extra 2 / External Inputs / Timers |
| 1101 | Extra operating mode | AV / Defrosting / Heat retention / Freeze protection / Cold recovery / Freezing / Emergency mode / Moisture reduction / Winter operation / Deflection / Rotor test / Start-up / Attendance |
| 1110 | Supply air temperature | °C |
| 1111 | Exhaust air temperature | °C |
| 1112 | Outdoor air temperature | °C |
| 1113 | Return temperature Water | °C (displayed if reheat is water coil) |
| 1120 | Moisture sensor Moisture content | % (displayed if sensor is present) |
| 1121 | Humidity sensor Temperature | °C (displayed if sensor is present) |
| 1130 | Air quality | ppm (displayed if sensor is present) |
| 1140 | Rotor Speed | rpm |
| 1142 | Rotor Efficiency | % (displayed if post-heating switched off) |
| 1150 | Supply air Fan control signal | % |
| 1151 | Supply air Fan speed | rpm (displayed if taco signal present) |
| 1152 | Supply air Pressure | Pa (displayed if sensor is present) |
| 1153 | Supply air Air flow | l/s (displayed if sensor is present) |
| 1160 | Extract air Fan control signal | % |
| 1161 | Exhaust air Fan speed | rpm (displayed if taco signal present) |
| 1162 | Exhaust air Pressure | Pa (displayed if sensor is present) |
| 1163 | Exhaust air Air flow | l/s (displayed if sensor is present) |
| 1170 | Control signal Heat recovery | % |
| 1171 | Control signal Heat | % |
| 1172 | Cooling control signal | % |
| 1180 | Electric battery | OFF / ON (displayed if electric battery is present) |
| 1181 | Preheating | OFF / ON (displayed if preheating is present) |
| 1182 | Circulation pump Heating | OFF / ON (displayed if water battery) |
| 1183 | Circulation pump Kyla | OFF / ON (shown if cooling pump) |
| 1200 | Operating time Aggregate | Hours |
| 1201 | (ModBus) | |
| 1202 | Total Power output VVX | % |
| 1203 | (ModBus) | |
| 1204 | Total Power output Post-heating | % |
| 1205 | (ModBus) | |
| 1206 | Total Power output Cooling | % |
| 1207 | (ModBus) | |
| 1208 | Operating time Int. Electric battery | Hours |
| 1209 | (ModBus) |