EvoControl Ventilation - Light - MPO
Models: A30T G3 Light, A60T G2 Light
The following parameters can be tested in test mode:
| Id | Text | Set/Read | Min | Max | Text values / ModBus | Unit |
|---|---|---|---|---|---|---|
| 5711 | Fan speed Supply air | Set of | -2 | 100 | -2 => 50%, -1 => 100% | % |
| 5712 | Supply air Fan speed | Read | 0 | 20000 | rpm | |
| 5714 | Fan speed Exhaust air | Set of | -2 | 100 | -2 => 50%, -1 => 100% | % |
| 5715 | Exhaust air Fan speed | Read | 0 | 20000 | rpm | |
| 5720 | Output VVX | Set of | -2 | 100 | -2 => 50%, -1 => 100% | % |
| 5722 | Output AfterHeat | Set of | 0 = Off, 1 = On | |||
| 5723 | Output Preheat | Set of | 0 = Off, 1 = On | |||
| 5725 | Output Alarm | Set of | 0 = Off, 1 = On | |||
| 5730 | Supply air temperature | Read | -50 | 70 | Decimal number | °C |
| 5731 | Exhaust air temperature | Read | -50 | 70 | Decimal number | °C |
| 5732 | Outdoor air temperature | Read | -50 | 70 | Decimal number | °C |
| 5733 | Exhaust air temperature | Read | -50 | 70 | Decimal number | °C |
| 5740 | Supply air efficiency | Read | 0 | 100 | % |