7.1.11 Test

The following parameters can be tested in test mode:

Modbus - Control & Reading
Id Text Set/Read Min Max Text values / ModBus Unit
5711 Fan speed Supply air Set of -2 100 -2 => 50%, -1 => 100% %
5712 Supply air Fan speed Read 0 20000 rpm
5714 Fan speed Exhaust air Set of -2 100 -2 => 50%, -1 => 100% %
5715 Exhaust air Fan speed Read 0 20000 rpm
5720 Output VVX Set of -2 100 -2 => 50%, -1 => 100% %
5722 Output AfterHeat Set of 0 = Off, 1 = On
5723 Output Preheat Set of 0 = Off, 1 = On
5725 Output Alarm Set of 0 = Off, 1 = On
5730 Supply air temperature Read -50 70 Decimal number °C
5731 Exhaust air temperature Read -50 70 Decimal number °C
5732 Outdoor air temperature Read -50 70 Decimal number °C
5733 Exhaust air temperature Read -50 70 Decimal number °C
5740 Supply air efficiency Read 0 100 %