EvoControl Ventilation - Counterflow
Models: Models coming soon
Post-heating is selected on parameter 240:
Av
Ext. electricity
- External electric heating battery (0-10 Volt), terminals 35 & 36.
- Own electrical supply and working switch required.
Int. El
- Internal electric heating battery.
- Alt. external electric heating battery with on/off control.
- Max load terminal 16-17, 230 Vac / 10 A.
water
- Control signal (0-10 Volt), terminals 35 & 36.
- Supply of actuator 24 Vdc is available, terminal 33 & 34.
- Circulation pump heating, 230 Vac (max 10A), terminals 16 & 17.
- Exercise run of pump.
- Freeze sensor required (accessory), terminals 47 & 48.
Mixed signal
See wiring diagram.
Depending on the unit, an internal electric battery may be included as standard.