6.10 Reheating

Post-heating is selected on parameter 240:

Av

  • No reheating.

Ext. electricity

  • External electric heating battery (0-10 Volt), terminals 35 & 36.
  • Own electrical supply and working switch required.

Int. El

  • Internal electric heating battery.
  • Alt. external electric heating battery with on/off control.
  • Max load terminal 16-17, 230 Vac / 10 A.

water

  • Control signal (0-10 Volt), terminals 35 & 36.
  • Supply of actuator 24 Vdc is available, terminal 33 & 34.
  • Circulation pump heating, 230 Vac (max 10A), terminals 16 & 17.
  • Exercise run of pump.
  • Freeze sensor required (accessory), terminals 47 & 48.

Mixed signal

See wiring diagram.

Depending on the unit, an internal electric battery may be included as standard.