Models: C125T G1, C250T G1

7.1.6 Alarm settings

900 - 953 Alarm setting

Alarms can be switched off and in three different categories:

  • Off = Alarm switched off.
  • A-Alarm = Stop of unit (see also emergency alarm), acknowledgement required.
  • B-Alarm = No stop of unit, acknowledgement required.
  • C-Alarm = Non-stop of unit, automatic acknowledgement when fault reset or manual acknowledgement.

Setting of alarm delay.

Alarm codes

  • 1B Communication Display
  • 2C Network, TCP/IP
  • 3C Internet connection
  • 4C Cloud service
  • 5A Fan Supply air
  • 6A Fan Exhaust air
  • 8A Freeze alarm Return circuit
  • 9A Low supply air temperature
  • 10A Low Exhaust Air Temp
  • 11A Temp sensor Supply air
  • 13A Outdoor air temperature sensor
  • 14A Temp sensor Freeze guard
  • 15B Moisture sensor
  • 16B Pressure value Supply air
  • 17B Exhaust air pressure value
  • 18C Fire
  • 19B High Reheat Temp
  • 24A Temperature sensor Exhaust air
  • 25B Low AL Temperature
  • 26B High AL Temperature
  • 27B Low TL Fan AL

Reservation for errors or linguistic discrepancies that may have arisen during printing, translation or assisted text processing. In case of discrepancies between language versions, the original Swedish version applies. See conditions.