Go to content

EvoControl Ventilation - Counterflow

Models: C125T G1, C250T G1

6.5.1 Function

If the alarm is active or unacknowledged, the alarm symbol appears at the top of the display and the alarm is added to the alarm list.

A-alarm

  • The unit stops *1.
  • Manual acknowledgement of alarms is required, and faults must be cleared before restart *2.

*1 If Standby, parameter 480 is activated (setting = Yes, see parameter list), the extract air fan and heat exchanger continue to run provided that the extract air fan has not alarmed.

*2 To exit Standby mode, the fault must be cleared and acknowledged, then the unit must be Stopped before restarting.

B-alarm

  • The unit continues to run.
  • Manual acknowledgement of alarms

C-alarm

  • The unit continues to run.
  • Automatic acknowledgement when alarm returns to normal or manual acknowledgement of alarm.

Reservation for errors or linguistic discrepancies that may have arisen during printing, translation or assisted text processing. In case of discrepancies between language versions, the original Swedish version applies. See conditions.

© 2026 Acetec AB. All rights reserved.