| Id | Text | ModBus | Level | Min | Max | Text values / ModBus | Factory value | Unit |
|---|---|---|---|---|---|---|---|---|
| 1100 | Drift mode | 3 | 0 | 0=Standby, 1=Stop, 2=Save, 3=Comfort, 4=Forced, 5=Overpressure, 6=Forced Time, 7=External Stop, 8=External Save, 9=External Comfort, 10=External Forced, 11=External 1, 12=External 2, 13=External Fire 1, 14=External Fire 2 |
STOP | |||
| 1102 | Extra operating mode | 3 | 0 | 0 | 2147483647 | (Bit mask, 1=active; several may be active at the same time) 0=Start-up, 1=Standby mode, 2=Defrost, 3=Cooling boost, 4=Cooling recovery, 5=Free cooling, 6=Winter operation, 7=Humidity reduction, 8=Occupancy, 9=De-icing, 10=Rotor test, 11=Rotor exercise |
0 | bit |
| 1103 | (ModBus) | 3 | 0 | |||||
| 1108 | Notification | 3 | 0 | 0 | 2147483647 | “(Bit mask, 1=active; several may be active at the same time) 0=Service,” | 0 | bit |
| 1109 | (ModBus) | 3 | 0 | |||||
| 1110 | Supply air temperature | 3 | 0 | -50 | 150 | Decimal number | 0 | °C |
| 1111 | Exhaust air temperature | 3 | 0 | -50 | 150 | Decimal number | 0 | °C |
| 1112 | Outdoor air temperature | 3 | 0 | -50 | 150 | Decimal number | 0 | °C |
| 1113 | Exhaust air temperature | 3 | 0 | -50 | 150 | Decimal number | 0 | °C |
| 1120 | Moisture sensor Moisture content | 3 | 0 | 0 | 100 | 0 | % | |
| 1121 | Humidity sensor Temperature | 3 | 0 | -50 | 150 | Decimal number | 0 | °C |
| 1150 | Supply air Fan control signal | 3 | 0 | 0 | 100 | 0 | % | |
| 1151 | Supply air Fan speed | 3 | 2 | 0 | 20000 | 0 | rpm | |
| 1160 | Extract air Fan control signal | 3 | 0 | 0 | 100 | 0 | % | |
| 1161 | Exhaust air Fan speed | 3 | 2 | 0 | 20000 | 0 | rpm | |
| 1170 | Control signal Heat recovery | 3 | 0 | 0 | 100 | 0 | % | |
| 1175 | Rotor Efficiency | 2 | -1 | 100 | Efficiency is only displayed if post-heating and pre-heating are switched off and Control signal VVX > 10% and UL is 5°C < TL & FL. Formula (((Temp TL – Temp UL) / (Temp FL – Temp UL)) * 100) |
-1 | % | |
| 1180 | Electric battery | 3 | 0 | 0=Off, 1=On | OFF | |||
| 1181 | Preheating | 3 | 0 | 0=Off, 1=On | OFF | |||
| 1200 | Operating time Aggregate | 3 | 0 | 0 | 32485 | 0 | d | |
| 1202 | Total Power output VVX | 3 | 0 | 0 | 100 | 0 | % | |
| 1210 | Operating time Int. Electric battery | 3 | 0 | 0 | 100 | 0 | % | |
| 1212 | Operating time Int. Electric battery | 3 | 0 | 0 | 100 | 0 | % |