5.3 Alarms

There are a number of alarms as shown in the table below:

Alarm Dehumidifier Fan on Acknowledged Cause Action
The processor card has lost contact with the display If necessary According to inst. car Problem with processor card, display or cable Check cables and connectors, new cards if necessary
The display has lost contact with the processor board If necessary According to inst. car Problem with processor card, display or cable Check cables and connectors, new cards if necessary
Climate alarm Yes Yes Yes Moisture content above the alarm curve for x number of days Check function
High temperature alarm No, it is not. No, it is not. Auto (*1, *2) Process air temperature (ambient temperature) higher than set value Check temperature and increase set value if necessary
Maintenance If necessary According to inst. Yes Long time since last maintenance Carry out service
Database error If necessary According to inst. car Programme versions in processor board and display mismatch New processor card and display needed
Moisture sensor, fault No, it is not. No, it is not. car Moisture sensor on the processor board broken New processor card needed

Note:
(*1) 3°K hysteresis.
(*2) Processor card versions prior to 1.0.3 must be de-energised to acknowledge high temperature alarms.