Go to content

EvoDry EDC 1.0 Dehumidifier - MPO

Models: PD, PDX, PD+, 6-24P, RCF 12-20 G1

5.1 Moisture

There are two types of humidity settings:

1. humidity setting:

  • Set the desired maximum relative humidity in .
    The dehumidifier dehumidifies as long as the moisture content is above the set value.
    Hystersen is +- 2.

From software version 1.3.0 the hysteresis is adjustable!

  • Constantly on.
    Dehumidification is constantly taking place.
  • Constantly off.
    Dehumidification never starts.

2. humidity control:

  • RF.
    Dehumidification starts when the relative humidity of the air exceeds the set value.
  • RF + Temp.
    Dehumidification starts when the relative humidity of the air exceeds the set value at temperatures above +15°C.
    The moisture content is allowed to rise by 1%/°C at temperatures below +15°C before dehumidification starts.
    The function is only active in the temperature range 0-15°C.
    At temperatures below 0°C, the curves continue horizontally, i.e. the moisture content is allowed to be 15% above the set value no matter how cold it gets.

Reservation for errors or linguistic discrepancies that may have arisen during printing, translation or assisted text processing. In case of discrepancies between language versions, the original Swedish version applies. See conditions.