7.3 Parameter list

Depending on the settings, not all parameters are always displayed!
Depending on the programme version, not all parameters are always available!
Some functions/parameters require accessories!
The minimum, maximum and default values of the parameters may vary slightly depending on the programme version!

New parameter Id for “Time clock” (Id 8000->) and “Alarm / Alarm history” (Id 9000->) as of 2024-10-22.

Column explanation:
Id = Parameter id, used for communication with ModBus.
ModBus = ModBus register type (Input / Holding register).
Level = User level in display (0=all, 1=simple, 2=advanced).
Text values / ModBus = Explanation of a value.

Parameter list
Fan
Id Text ModBus Level Min Max Text values / ModBus Factory value Unit
100 Location Supply air fan 4 2 0=Lower (A1&A2=Right), 1=Upper (A1&A2=Left) 1=Upper 0
105 Restrict Fan Control 4 2 30 100 0 100 %
106 Pulses per lap 0 2 1 10 0 1 ppr
110 Fan speed Supply air Saving 4 1 20 100 0 30 %
111 Fan speed Exhaust air Saving 4 1 20 100 0 40 %
112 Fan speed Supply air Comfort 4 1 20 100 0 45 %
113 Fan speed Exhaust air Comfort 4 1 20 100 0 60 %
114 Fan speed Supply air Forcing 4 1 20 100 0 60 %
115 Fan speed Exhaust air Forcing 4 1 20 100 0 80 %
116 Fan speed Supply air External 1 4 1 20 100 0 45 %
117 Fan speed Exhaust air External 1 4 1 20 100 0 60 %
118 Fan speed Supply air External 2 4 1 20 100 0 45 %
119 Fan speed Exhaust air External 2 4 1 20 100 0 60 %
130 Pressurise Supply Air Save 4 1 15 2000 0 20 Pa
131 Pressure Exhaust air Saving 4 1 15 2000 0 30 Pa
132 Pressure Supply air Comfort 4 1 15 2000 0 45 Pa
133 Pressure Exhaust air Comfort 4 1 15 2000 0 80 Pa
134 Pressure Supply air Forcing 4 1 15 2000 0 80 Pa
135 Pressure Exhaust air Forcing 4 1 15 2000 0 150 Pa
136 Pressure Supply air External 1 4 1 15 2000 0 45 Pa
137 Pressure Exhaust air External 1 4 1 15 2000 0 80 Pa
138 Pressure Supply air External 2 4 1 15 2000 0 45 Pa
139 Pressure Exhaust air External 2 4 1 15 2000 0 80 Pa
150 Flow Supply air Saving 4 1 10 10000 0 200 l/s
151 Flow Exhaust air Savings 4 1 10 10000 0 300 l/s
152 Flow Supply air Comfort 4 1 10 10000 0 450 l/s
153 Flow rate Exhaust air Comfort 4 1 10 10000 0 800 l/s
154 Flow Supply air Forcing 4 1 10 10000 0 800 l/s
155 Flow Exhaust air Forcing 4 1 10 10000 0 1500 l/s
156 Flow rate Supply air External 1 4 1 10 10000 0 500 l/s
157 Flow rate Exhaust air External 1 4 1 10 10000 0 1000 l/s
158 Flow rate Supply air External 2 4 1 10 10000 0 500 l/s
159 Flow rate Exhaust air External 2 4 1 10 10000 0 1000 l/s
temperature
Id Text ModBus Level Min Max Text values / ModBus Factory value Unit
200 Controller type 4 1 0=On, 1=Off, 2=Auto, 3=FRT 0=To 0
201 Switching temp Controller type 4 1 -10 10 0 5 °C
205 Neutralzone Kyla 4 2 1 10 Decimal number 2 °K
210 Temperature Savings 4 1 10 40 0 20 °C
211 Temperature Comfort 4 1 10 40 0 20 °C
212 Temperature Forcing 4 1 10 40 0 20 °C
213 Temperature External 1 4 1 10 40 0 20 °C
214 External temperature 2 4 1 10 40 0 20 °C
220 Temperature Savings FRT 4 1 -5 5 0 -2 °K
221 Temperature Comfort FRT 4 1 -5 5 0 -2 °K
222 Temperature Forcing FRT 4 1 -5 5 0 -2 °K
223 Temperature External 1 FRT 4 1 -5 5 0 -2 °K
224 Temperature External 2 FRT 4 1 -5 5 0 -2 °K
230 Outdoor compensation at -20°C 4 1 -5 5 0 0 °K
231 Outdoor compensation at 0°C 4 1 -5 5 0 0 °K
232 Outdoor compensation at +40°C 4 1 -10 10 0 0 °K
240 Reheat 4 1 0=Off, 1=Ext. Electricity, 2=Int. Electricity, 3=Water, 4=Mixed sign. 2=Int. Elbatt 0
241 Hysteresis EVB 4 2 0,5 2 Decimal number 1 °K
245 Heat retention Water temp 4 2 10 30 0 20 °C
246 Freeze monitor Alarm limit 4 2 5 15 0 7 °C
248 Cooling signal 4 1 0=Off, 1=On 1=On 0
250 Preheating / Cooling pump / EvoCool 4 1 0=Off, 1=Preheating, 2=Cooling pump, 3=EvoCool 0=Off 0
251 Utetemp, Activation Preheating 4 1 -25 0 0 -15 °C
260 Supply air regulator P-band 4 2 10 300 0 50 °K
261 Supply air controller I-time 4 2 20 600 0 100 s
262 Minbegr Supply air temperature 4 2 10 25 0 10 °C
263 Maxbegr Supply air temperature 4 2 15 50 0 40 °C
264 Low temperature alarm Supply air 4 2 -20 15 0 5 °C
266 High temperature alarm Post-heating 4 2 1 10 0 4 °K
270 Off/Room controller P-band 4 2 1 300 0 4 °K
271 Off/Room controller I-time 4 2 10 1800 0 300 s
272 Off/Rum cascade factor 4 2 2 10 0 5 °K
273 Low temperature alarm Exhaust air 4 2 -20 15 0 10 °C
Extra credit
Id Text ModBus Level Min Max Text values / ModBus Factory value Unit
300 Moisture sensor 4 1 0=Off, 1=On 0=Off 0
301 Setpoint Moisture 4 1 20 90 0 60 %
302 Capacity increase Moisture management 4 1 -20 100 0 30 %
303 Coupling diff Humidity control 4 2 3 15 0 5 %
304 Control signal VVX for humidity control 4 2 10 100 0 70 %
310 Pressure sensor Supply air 4 1 0=Off, 1=Pressure, 2=Flow, 3=Slave, 4=Measured pressure, 5=Measured flow. flow 0=Off 0
311 Pressure sensor Exhaust air 4 1 0=Off, 1=Pressure, 2=Flow, 3=Slave, 4=Measured pressure, 5=Measured flow. flow 0=Off 0
312 Pressure sensor Measuring range 4 2 100 2500 0 300 Pa
313 Slave control Diff 4 1 -50 50 0 0 %
314 K-factor 4 2 1 1000 Decimal number 40 0
315 Pressure control P-Band / Setpoint 4 2 2 50 Decimal number 10 0
316 Pressure regulation I-Tid 4 2 20 300 0 30 s
317 Pressure control Alarm limit deviation +- 4 2 5 50 0 20 %
330 Air quality sensors 4 1 0=Off, 1=On 0=Off 0
331 Air quality sensors Measuring range 4 2 20 2000 0 2000 ppm
332 Air quality Setpoint 4 1 2 2000 0 800 ppm
333 Air quality Coupling diff 4 1 2 400 0 150 ppm
Features and functions
Id Text ModBus Level Min Max Text values / ModBus Factory value Unit
400 ECO mode 4 1 0=Off, 1=On 0=Off 0
401 ECO temperature 4 2 10 40 0 17 °C
410 Hot start Temp 4 1 -20 20 0 5 °C
411 Hot start Time 4 1 0 5 0 2 m
420 Fire function 4 2 1 4 0 1 0
430 Cooling forcing 4 1 0=Off, 1=On 0=Off 0
431 Increase in cooling capacity 4 2 0 100 0 30 %
435 Refrigeration recovery 4 1 0=Off, 1=On 0=Off 0
436 Cooling recovery Diff temp 4 2 1 5 0 2 °K
440 Free cooling via outdoor air 4 1 0=Off, 1=On 0=Off 0
441 Free cooling at outdoor air temperature 4 2 0 25 0 10 °C
442 Free cooling at exhaust air temperature 4 2 15 30 0 25 °C
450 Defrosting 4 1 0=Off, 1=On (All aggregates smaller than A390T are default=On) 0=Off 0
451 Defrosting Starts at Utetemp 4 2 -30 0 0 -10 °C
452 Defrosting time 4 2 2 30 0 20 m
453 Defrosting interval 4 2 30 600 0 180 m
454 VVX Control 4 2 0=Off, 1=On 1=On 0
455 Winter drift 4 1 0=Off, 1=On 0=Off 0
456 Winter operation Starts at Utetemp 4 2 -20 10 0 -5 °C
457 Winter operation Fan Supply air 4 2 -50 50 0 -20 %
458 Winter operation Fan Exhaust air 4 2 -50 50 0 20 %
459 Winter operation Moisture reduction Rotor 4 2 0 100 In case of moisture reduction, the residual value is 60% 0 %
460 Overpressure timer Time 4 1 0 30 0 15 m
461 Forcing hours Time 4 1 0 240 0 120 m
465 Presence, Switch-off delay 4 2 0 72 0=Off 0 h
466 Presence, Operating mode 4 2 0=External Economy, 1=External Comfort, 2=External Forced, 3=External 1, 4=External 2 1=External comfort 0
467 Presence, Operating mode Return 4 2 0=Standby, 1=Stop, 2=Save, 3=Comfort, 4=Forced, 5=Time 2=Savings 0
470 Order of priority, External Entrances 4 2 0=Prime, 1=Last 0=Prio 0
471 Prioritisation, External Stop 4 2 0=Prime, 1=Last 0=Prio 0
472 Prioritisation, External Fire 4 2 0=Prime, 1=Last 0=Prio 0
475 Engine type 0 2 0=Induction motor, 1=Stage motor (on/off), 2=Stage motor N17, 3=Stage motor N24 0=Induction motor 0
476 Stepper motor, Max shaft speed 0 2 20 400 0 90 rpm
477 Stepper motor, Current 0 2 -10 10 0 0 0
478 Stepper motor, Direction 0 2 0=CW, 1=CCW 0=CW 0
480 ReserveDrift 4 1 0=Off, 1=On 1=On 0
482 Exercise driving 4 2 0=Off, 1=On 1=On 0
Button lock
Id Text ModBus Level Min Max Text values / ModBus Factory value Unit
500 stop 4 1 0=Off, 1=On 0=Off
501 Spruce 4 1 0=Off, 1=On 0=Off 0
502 Comfort and convenience 4 1 0=Off, 1=On 0=Off 0
503 Forced 4 1 0=Off, 1=On 0=Off 0
504 Tidur 4 1 0=Off, 1=On 0=Off 0
505 Overpressure 4 1 0=Off, 1=On 0=Off 0
506 Forced timer 4 1 0=Off, 1=On 0=Off 0
507 ECO 4 1 0=Off, 1=On 0=Off 0
508 temperature 4 1 0=Off, 1=On 0=Off 0
520 Timer setting 4 1 0=Off, 1=On 0=Off 0
521 Alarm management 4 1 0=Off, 1=On 0=Off 0
Alarm settings
Id Text ModBus Level Min Max Text values / ModBus Factory value Unit
900 Communication Disp. 4 2 Id 1, 0=Off, 1=A alarm, 2=B alarm, 3=C alarm 2=B-alarm 0
901 Alarm delay, P900 4 2 30 6000 0 60 s
902 Network, TCP/IP 4 2 Id 2, 0=Off, 1=A alarm, 2=B alarm, 3=C alarm 3=C-alarm 0
903 Alarm delay, P902 4 2 60 6000 0 600 s
904 Internet connection 4 2 Id 3, 0=Off, 1=A alarm, 2=B alarm, 3=C alarm 3=C-alarm 0
905 Alarm delay, P904 4 2 60 6000 0 600 s
906 Cloud service 4 2 Id 4, 0=Off, 1=A alarm, 2=B alarm, 3=C alarm 3=C-alarm 0
907 Alarm delay, P906 4 2 60 6000 0 600 s
908 Fan Supply air 4 2 Id 5, 0=Off, 1=A alarm, 2=B alarm, 3=C alarm 1=A alarm 0
909 Alarm delay, P908 4 2 10 600 0 30 s
910 Fan Exhaust air 4 2 Id 6, 0=Off, 1=A alarm, 2=B alarm, 3=C alarm 1=A alarm 0
911 Alarm delay, P910 4 2 10 600 0 30 s
912 Heat exchangers 4 2 Id 7, 0=Off, 1=A alarm, 2=B alarm, 3=C alarm 1=A alarm 0
913 Alarm delay, P912 4 2 30 600 0 60 s
914 Freeze alarm Return circuit 4 2 Id 8, 0=Off, 1=A alarm, 2=B alarm, 3=C alarm 1=A alarm 0
915 Alarm delay, P914 4 2 5 30 0 5 s
916 Low supply air temperature 4 2 Id 9, 0=Off, 1=A alarm, 2=B alarm, 3=C alarm 1=A alarm 0
917 Alarm delay, P916 4 2 60 6000 0 6000 s
918 Low Exhaust air temp 4 2 Id 10, 0=Off, 1=A alarm, 2=B alarm, 3=C alarm 0=Off 0
919 Alarm delay, P918 4 2 60 6000 0 6000 s
920 Temperature sensor Supply air 4 2 Id 11, 0=Off, 1=A alarm, 2=B alarm, 3=C alarm 1=A alarm 0
921 Alarm delay, P920 4 2 5 30 0 5 s
922 Temperature sensor Exhaust air 4 2 Id 12, 0=Off, 1=A alarm, 2=B alarm, 3=C alarm 1=A alarm 0
923 Alarm delay, P922 4 2 5 30 0 5 s
924 Outdoor air temperature sensor 4 2 Id 13, 0=Off, 1=A alarm, 2=B alarm, 3=C alarm 1=A alarm 0
925 Alarm delay, P924 4 2 5 30 0 5 s
926 Temp sensor Freeze guard 4 2 Id 14, 0=Off, 1=A alarm, 2=B alarm, 3=C alarm 1=A alarm 0
927 Alarm delay, P926 4 2 5 30 0 5 s
928 Moisture sensor 4 2 Id 15, 0=Off, 1=A alarm, 2=B alarm, 3=C alarm 2=B-alarm 0
929 Alarm delay, P928 4 2 30 6000 0 60 s
930 Pressure value Supply air 4 2 Id 16, 0=Off, 1=A alarm, 2=B alarm, 3=C alarm 2=B-alarm 0
931 Alarm delay, P930 4 2 60 6000 0 600 s
932 Pressure value Exhaust air 4 2 Id 17, 0=Off, 1=A alarm, 2=B alarm, 3=C alarm 2=B-alarm 0
933 Alarm delay, P932 4 2 60 6000 0 600 s
934 fire 4 2 Id 18, 0=Off, 1=A alarm, 2=B alarm, 3=C alarm 3=C-alarm 0
935 Alarm delay, P934 4 2 5 30 0 5 s
936 High Reheat Temp 4 2 Id 19, 0=Off, 1=A alarm, 2=B alarm, 3=C alarm 2=B-alarm 0
937 Alarm delay, P936 4 2 600 9000 0 5400 s
944 Communication Stegm. 4 2 Id 23, 0=Off, 1=A alarm, 2=B alarm, 3=C alarm 2=B-alarm 0
945 Alarm delay, P944 4 2 30 6000 0 60 s
Mixed
Id Text ModBus Level Min Max Text values / ModBus Factory value Unit
1000 Rotor 3 100 0=Off, 1=On 0=Off 0
1001 Heating 3 100 0=Off, 1=On 0=Off 0
1002 Kyla 3 100 0=Off, 1=On 0=Off 0
1003 Alarm 3 100 0=Off, 1=A alarm, 2=B alarm, 3=C alarm 0=Off 0
1004 Cloud service 3 100 0=Off, 1=Not connected, 2=Connected, 3=Remote, 4=Remote time 0=Off 0
1005 Network, TCP/IP 3 100 0=Off, 1=No cable, 2=Connected, 3=Internet 0=Off 0
1010 Fashion rules 4 1 0=Standby, 1=Stop, 2=Save, 3=Comfort, 4=Forced, 5=Overpressure, 6=Forced Time, 7=External Fire, 8=External Stop, 9=External Save, 10=External Comfort, 11=External Forced, 12=External 1, 13=External 2, 14=Time Off, 15=Time Saving, 16=Time Comfort, 17=Time Forced, 18=Time External 1, 19=Time External 2, 20=Time Saving AirQ, 21=Time Comf. AirQ, 22=Tidur Forc. AirQ 1=Stop 0
1015 Special rules mother 3 100 0=Off, 1=Defrost, 2=Keeping warm, 3=Freeze protection, 4=Cooling recovery, 5=Free cooling, 6=Reserve operation, 7=Moisture reduction, 8=Winter operation, 9=Display, 10=Root test, 11=Start-up, 12=Presence 0=Off 0
1016 Tidur 4 1 0=Off, 1=On 0=Off 0
1017 ECO 4 1 0=Off, 1=On 0=Off 0
1021 Date of last service 4 1 -1 2147483647 -1=Service not done -1 Epoch
1022 (ModBus) 4 1 0 0 0
1023 Service interval 4 1 0 36 0 12 m
1024 Days to next service 3 100 -1 99999 -1=Time for service -1 d
Measurement values
Id Text ModBus Level Min Max Text values / ModBus Factory value Unit
1100 Drift mode 3 0 0=Standby, 1=Stop, 2=Save, 3=Comfort, 4=Forced, 5=Overpressure, 6=Forced Time, 7=External Fire, 8=External Stop, 9=External Save, 10=External Comfort, 11=External Forced, 12=External 1, 13=External 2, 14=Time Off, 15=Time Saving, 16=Time Comfort, 17=Time Forced, 18=Time External 1, 19=Time External 2, 20=Time Saving AirQ, 21=Time Comf. AirQ, 22=Tidur Forc. AirQ 1=Stop 0
1101 Extra operating mode 3 0 0=Off, 1=Defrost, 2=Keeping warm, 3=Freeze protection, 4=Cooling recovery, 5=Free cooling, 6=Reserve operation, 7=Moisture reduction, 8=Winter operation, 9=Display, 10=Root test, 11=Start-up, 12=Presence 0=Off 0
1110 Supply air temperature 3 0 -50 70 Decimal number 0 °C
1111 Exhaust air temperature 3 0 -50 70 Decimal number 0 °C
1112 Outdoor air temperature 3 0 -50 70 Decimal number 0 °C
1113 Return temperature Water 3 0 -50 70 Decimal number 0 °C
1120 Moisture sensor Moisture content 3 0 0 100 0 0 %
1121 Humidity sensor Temperature 3 0 -50 150 Decimal number 0 °C
1130 Air quality 3 0 0 2000 0 0 ppm
1140 Rotor Speed 3 0 0 100 Decimal number 0 rpm
1142 Rotor Efficiency 0 0 -1 100 Only when reheat = Off. (((Temp TL - Temp UL) / (Temp FL - Temp UL)) * 100) -1 %
1150 Supply air Fan control signal 3 0 0 100 0 0 %
1151 Supply air Fan speed 3 0 0 20000 0 0 rpm
1152 Supply air Pressure 3 0 0 5000 0 0 Pa
1153 Supply air Air flow 3 0 0 30000 0 0 l/s
1160 Extract air Fan control signal 3 0 0 100 0 0 %
1161 Exhaust air Fan speed 3 0 0 20000 0 0 rpm
1162 Exhaust air Pressure 3 0 0 5000 0 0 Pa
1163 Exhaust air Air flow 3 0 0 30000 0 0 l/s
1170 Control signal Heat recovery 3 0 0 100 0 0 %
1171 Control signal Heat 3 0 0 100 0 0 %
1172 Cooling control signal 3 0 0 100 0 0 %
1180 Electric battery 3 0 0=Off, 1=On 0=Off 0
1181 Preheating 3 0 0=Off, 1=On 0=Off 0
1182 Circulation pump Heating 3 0 0=Off, 1=On 0=Off 0
1183 Circulation pump Kyla 3 0 0=Off, 1=On 0=Off 0
1200 Operating time Aggregate 3 0 0 2147483647 0 0 h
1201 (ModBus) 3 0 0 0 0
1202 Total Power output VVX 3 0 0 2147483647 0 0 %
1203 (ModBus) 3 0 0 0 0
1204 Total Power output Post-heating 3 0 0 2147483647 0 0 %
1205 (ModBus) 3 0 0 0 0
1206 Total Power output Cooling 3 0 0 2147483647 0 0 %
1207 (ModBus) 3 0 0 0 0
1208 Operating time Int. Electric battery 3 0 0 2147483647 0 0 h
1209 (ModBus) 3 0 0 0 0
Display
Id Text ModBus Level Min Max Text values / ModBus Factory value Unit
5100 Language 4 1 0=Swedish, 1=English 0=Swedish 0
5110 Display Brightness 4 1 10 100 0 100 %
5111 Screen saver 4 1 0=Off, 1=Logo 1=Logo 0
5120 Time zone GMT 4 1 0 2 0 1 0
5121 Set time 4 1 -2147483647 2147483647 Automatically resets to 0 0 Epoch
5122 (ModBus) 4 1 0 0 0
Help for display
Id Text ModBus Level Min Max Text values / ModBus Factory value Unit
5130 Year 0 1 1970 2038 0 2025 0
5131 Month 0 1 0=January, 1=February, 2=March, 3=April, 4=May, 5=June, 6=July, 7=August, 8=September, 9=October, 10=November, 11=December 0=January 0
5132 Day 0 1 1 31 0 1 0
5133 Hour 0 1 0 23 0 0 0
5134 minute 0 1 0 59 0 0 0
5135 Second 0 1 0 59 0 0 0
Systems / Networks
Id Text ModBus Level Min Max Text values / ModBus Factory value Unit
5200 Network connectivity 0 1 0=Off, 1=On 1=On 0
5201 Get IP address From 0 1 0=DHCP, 1=Static 0=DHCP 0
5202 Static IP address (a) 0 1 0 255 0 0 0
5203 (b) 0 1 0 255 0 0 0
5204 © 0 1 0 255 0 0 0
5205 (d) 0 1 0 255 0 0 0
5206 Static Net Worm (a) 0 1 0 255 0 255 0
5207 (b) 0 1 0 255 0 255 0
5208 © 0 1 0 255 0 255 0
5209 (d) 0 1 0 255 0 0 0
5210 Static Gateway IP address (a) 0 1 0 255 0 0 0
5211 (b) 0 1 0 255 0 0 0
5212 © 0 1 0 255 0 0 0
5213 (d) 0 1 0 255 0 0 0
5214 Static DNS IP address (a) 0 1 0 255 0 0 0
5215 (b) 0 1 0 255 0 0 0
5216 © 0 1 0 255 0 0 0
5217 (d) 0 1 0 255 0 0 0
5220 Auto. Restart 4 1 0=Off, 1=On 1=On 0
5240 Connect to EvoCloud 4 1 0=Off, 1=On 1=On 0
5241 Allow remote control 4 1 0=Off, 1=Yes, 2=Time 0=Off 0
5242 Remote control time 4 1 1 720 0 72 h
5290 Restarting the genset 4 1 “0=No, 1=Yes,
(Automatically reset to 0)”
0=No 0
Recovery
Id Text ModBus Level Min Max Text values / ModBus Factory value Unit
5300 Fan 0 1 “0=No, 1=Level 1, 2=Level 2, 3=Level 1 & 2,
(Automatically reset to 0)”
0=No 0
5301 temperature 0 1 “0=No, 1=Level 1, 2=Level 2, 3=Level 1 & 2,
(Automatically reset to 0)”
0=No 0
5302 Extra credit 0 1 “0=No, 1=Level 1, 2=Level 2, 3=Level 1 & 2,
(Automatically reset to 0)”
0=No 0
5303 Features and functions 0 1 “0=No, 1=Level 1, 2=Level 2, 3=Level 1 & 2,
(Automatically reset to 0)”
0=No 0
5304 Button lock 0 1 “0=No, 1=Level 1, 2=Level 2, 3=Level 1 & 2,
(Automatically reset to 0)”
0=No 0
5305 Alarm settings 0 1 “0=No, 1=Level 1, 2=Level 2, 3=Level 1 & 2,
(Automatically reset to 0)”
0=No 0
System information
Id Text ModBus Level Min Max Text values / ModBus Factory value Unit
5400 Current time 3 100 -2147483647 2147483647 0 1735693200 Epoch
5401 (ModBus) 3 100 0 0 0
5410 Model designation 0 100 0 0
5411 Serial number 0 100 0 0
5412 Article number 0 100 0 0
5413 Programme version DUC 0 100 0 0
5414 Bootloader version DUC 0 100 0 0
5415 Programme version Display 0 100 0 0
5416 Bootloader version Display 0 100 0 0
5417 Registration code EvoCloud 0 100 0 0
5418 Security code EvoCloud 0 100 -1 65535 0 0
5420 Database version 0 100 0 0.5.25
5422 Inspected 3 100 -2147483647 2147483647 0 Epoch
5423 (ModBus) 3 100 0 0
5424 Operational 3 100 -2147483647 2147483647 0 Epoch
5425 (ModBus) 3 100 0 0
5430 MAC address 0 100 0 0
5431 IP address 0 100 0 0
5432 Fishnet 0 100 0 0
5433 Gateway address 0 100 0 0
5434 Ethernet link 3 100 0=Down, 1=Up 0=Down 0
5435 Connected to the Internet 3 100 0=No, 1=Yes 0=No 0
5440 Connected to EvoCloud 3 100 0=No, 1=Yes 0=No 0
5450 Alarm type Fans 0 100 0=Relay, 1=Taco (A390T and larger units have relay output) 1=Taco 0
Test
Id Text ModBus Level Min Max Text values / ModBus Factory value Unit
5700 Test mode 0 0 0=Off, 1=On 0=Off 0
5710 Dampers 0 0 0=Off, 1=On 0=Off 0
5711 Fan speed Supply air 0 0 0 100 0 0 %
5712 Supply air Fan speed 0 0 0 20000 0 0 rpm
5713 Fan Supply air Alarm 0 0 0=Off, 1=On 0=Off 0
5714 Fan speed Exhaust air 0 0 0 100 0 0 %
5715 Exhaust air Fan speed 0 0 0 20000 0 0 rpm
5716 Fan Exhaust air Alarm 0 0 0=Off, 1=On 0=Off 0
5717 Output VVX 0 0 -1 100 -1=100% 0 %
5718 Heat exchanger Speed 0 0 0 100 Decimal number 0 rpm
5719 Output Heat 0 0 0 100 0 0 %
5720 Output Cold 0 0 0 100 0 0 %
5730 Supply air temperature 0 0 -50 70 Decimal number 0 °C
5731 Exhaust air temperature 0 0 -50 70 Decimal number 0 °C
5732 Outdoor air temperature 0 0 -50 70 Decimal number 0 °C
5733 Return temperature Water 0 0 -50 70 Decimal number 0 °C
5740 Supply air Pressure 0 0 0 100 Decimal number 0 %
5741 Exhaust air Pressure 0 0 0 100 Decimal number 0 %
5742 Air quality 0 0 0 100 Decimal number 0 %
5743 Extra a/d input 1 0 0 0 100 Decimal number 0 %
5744 Extra a/d entrance 2 0 0 0 100 Decimal number 0 %
Tidur
Id Text ModBus Level Min Max Text values / ModBus Factory value Unit
8xx0 Available 4 0 0=No, 1=Yes 0=No 0
8xx1 Active 4 0 0=No, 1=Yes 1=Yes 0
8xx2 Drift mode 4 0 0=Off, 1=Save, 2=Comfort, 3=Forced, 4=External 1, 5=External 2, 6=AirQ 0=Off 0
8xx3 Day of the week 4 0 0=Monday, 1=Tuesday, 2=Wednesday, 3=Thursday, 4=Friday, 5=Saturday, 6=Sunday, 7=All days, 8=Wednesdays, 9=Wednesdays 0=Monday 0
8xx4 Hour 4 0 0 23 0 0 0
8xx5 minute 4 0 0 59 0 0 0
xx number of timers, max 32 pcs 1 32 Replace xx with the location of the clock
Alarm
Id Text ModBus Level Min Max Text values / ModBus Factory value Unit
9001 Active alarms (alarm time 1-32) 3 99 0 2147483647 Bit, id from alarm settings, ex. 0×0010h=id 5 0 bit
9002 (ModBus) (larmid 17-32) 3 99 ex. 0×0010h=id 21 0 0
9003 Active alarms (alarm time 33-64) 3 99 0 2147483647 Bit, id from alarm settings, ex. 0×0010h=id 37 0 bit
9004 (ModBus) (larmid 49-64) 3 99 ex. 0×0010h=id 53 0 0
9005 Clear alarm history 4 0 0=No, 1=Yes (automatically reset to 0) 0=No 0
Alarm scheme Last alarm yy=01, second last yy=02 etc.
9yy1 Alarm code 3 0 0 2147483647 Id from alarm settings 0 0
9yy2 Alarm time 3 0 0 2147483647 Latest alert 0 Epoch
9yy3 (ModBus) 3 0 0 0 0
9yy4 Receipt time 4 0 0 2147483647 0=No Ack, 1=Ack (sets current time), 2=Auto Ack, 3 >= Ack time in Epoch 0 Epoch
9yy5 (ModBus) 4 0 0 0 0
yy number of alarms, max 32 1 32 Replace yy with the alarm location

Reservation for errors or linguistic discrepancies that may have arisen during printing, translation or assisted text processing. In case of discrepancies between language versions, the original Swedish version applies. See conditions.