7.1.2 Temperatures
210 - 214 Setpoint temperature
Setting the desired supply air temperature in different operating modes.
220 Reheat
By:
- Reheat not active.
On:
- Pulse control of internal electric battery via relay output.
- The rotor must have been constantly switched on for 3 minutes before the electric battery is switched on for the first time.
230 Pre-heater
By:
- Pre-heating is not active.
On:
- In Preheating mode, the relay output is activated when the outside air temperature falls below the set value.
- Fixed hysteresis +/- 2°C.
231 Capitalisation of purchasers
Outdoor temperature for activation of preheater.
242 Minimum limit
Minimum supply air temperature limitation (applicable in all control modes).
243 Maximum limitation
Maximum limitation of supply air temperature (applicable in all control modes).
245 Low temperature alarm supply air
If the supply air temperature falls below the set value, an alarm will sound after a certain period of time.
246 High temperature alarm Post-heating
If the supply air temperature exceeds the set value and there is no need for reheating, the alarm will clear after a certain period of time.
255 Low temperature alarm exhaust air
If the extract air temperature falls below the set value, an alarm will sound after a certain period of time.