7.1.2 Temperatures

210 - 214 Setpoint temperature

Setting the desired supply air temperature in different operating modes.

220 Reheat

By:

  • Reheat not active.

On:

  • Pulse control of internal electric battery via relay output.
  • The rotor must have been constantly switched on for 3 minutes before the electric battery is switched on for the first time.

230 Pre-heater

By:

  • Pre-heating is not active.

On:

  • In Preheating mode, the relay output is activated when the outside air temperature falls below the set value.
  • Fixed hysteresis +/- 2°C.

231 Capitalisation of purchasers

Outdoor temperature for activation of preheater.

242 Minimum limit

Minimum supply air temperature limitation (applicable in all control modes).

243 Maximum limitation

Maximum limitation of supply air temperature (applicable in all control modes).

245 Low temperature alarm supply air

If the supply air temperature falls below the set value, an alarm will sound after a certain period of time.

246 High temperature alarm Post-heating

If the supply air temperature exceeds the set value and there is no need for reheating, the alarm will clear after a certain period of time.

255 Low temperature alarm exhaust air

If the extract air temperature falls below the set value, an alarm will sound after a certain period of time.