EvoControl Ventilation - Light - MPO

Models: A30T G3 Light, A60T G2 Light

6.2 Start-up / Start-up sequence

When an operating mode is selected in the ventilation unit, the extract fan and the heat exchanger start first.
The supply air fan has a start delay of at least 30 seconds.

The start-up may last longer than the set values:

  • When control is waiting for signals from fans, it can take up to 10 minutes.
  • When control is waiting for signals from the heat exchanger, see Description - Heat recovery.