6.4.4 Back-up operation

In case of an A-alarm that normally stops the unit and Reserve operation activated in parameter 480, the unit's extract air fan continues to run.

Indicated by the display of “Standby” at the top of the control panel.

  • Supply air fan = Off.
  • Exhaust air fan = On (capacity according to factory settings in each operating mode in %).
  • Rotor = On.
  • Reheat battery = Off.
  • Preheating battery = Off.