7.1.4 Features
410 ECO, Start delay dehumidification.
Start delay before dehumidification starts.
411 Start delay heating step 2.
Start delay before heating stage 2 starts.
420 Fire function.
The function is activated when the end between terminals 9 and 10 is broken.
Selectable in two modes:
- Process air fan stopped, control air fan stopped. Damper closing. Heater and rotor outputs off.
- Process air fan stopped, control air fan at 100 per cent. Damper opens. Heater and rotor outputs off.
430 Min Temp Increase, Dehumidification On.
Low temperature rise alarm on wet air during dehumidification on.
431 High Temp Increase, Dehumidification Off.
Alarm in case of high temperature rise of wet air during dehumidification of.
432 High Pro Temp.
High process air temperature alarm.
440 Humidity deviation signal, Start.
Starting point for moisture deviation in relative humidity (RH) control.
441 Humidity deviation signal, Area.
Moisture deviation range for relative humidity (RH) control.
442 Humidity deviation signal, Start.
Starting point for moisture deviation in absolute humidity (AH) control.
443 Humidity deviation signal, Area.
Moisture deviation range for absolute humidity (AH) control.
444 Humidity deviation signal, Start.
Starting point for moisture deviation at dew point (DP) control.
445 Humidity deviation signal, Area.
Moisture deviation range for dew point (DP) control.
446 Humidity deviation signal, Start.
Humidity deviation starting point for active dew point (ADP) control.
447 Humidity deviation signal, Area.
Moisture deviation range for active dew point (ADP) control.
450 Rotor On time.
Rotor running time (pulse).
Calibrated at the factory, should not be changed!
451 Rotor Off time.
Rotor stop time (pulse).
Calibrated at the factory, should not be changed!
453 Rotor Post-drying, Time.
Stops the rotor and dries out the dehumidifier for the set time.
454 Rotor Drying, Start temperature.
Starting temperature for post-drying.
455 Rotor Cooling.
Cools down the dehumidifier after dehumidification.
460 Forcing hours.
Operation mode forcing active for the time set in the parameter. Returns to the previous operating mode after the set time.
470 Prioritisation.
Operating mode:
- Fire function, terminals 9 & 10 open.
- Stop, terminal 7 & 8 open.
- High, terminal 1 & 4 closed.
- Middle, terminal 1 & 3 closed.
- Low, terminal 1 & 2 closed.
- Display.
If the priority order, parameter 470-472, is set to “Priority”, the order as above applies if more inputs are active.
If the priority order, parameters 470-472, is set to “Last input”, the last command is valid until the next command.
If parameter 470 is “Prio”, parameters 471-472 are automatically set to “Prio” as well and become hidden in the control panel.
480 Standby / Emergency
In case of A-alarm which normally stops the dehumidifier and Standby mode activated in parameter 480, the dehumidifier continues in the set operating mode according to Reserve drift.