EvoControl Pro series

Models: EvoDry 30 Pro – 180 Pro

7.1.1 Fan

100 Fan control mode.

Constant operation of the process air fan or stop when the moisture content falls below the setpoint.

110–112 Fan capacity.

Process fan capacity in different operating conditions

120 Regeneration fan, Slave / Offset.

Regeneration fan offset from process fan.

Calibrated at the factory, should not be changed!

121 Reg. fan, Stop delay.

Delayed stop of the regeneration fan when the moisture content falls below the setpoint. Can be selected to be constantly on.

122 Reg. fan, constant capacity.

Capacity of the regeneration fan when the moisture content is below the setpoint and selected constant on in parameter 121.

130 – 132 Fan Auto, humidity deviation/speed.

Humidity deviation from setpoint, e.g. Setpoint 60 % and set value of 3 %:

When the actual value rises above 60 %, the fans start at low speed.
When the actual value rises above 63 %, the fans increase to intermediate speed.
When the actual value rises above 66 %, the fans increase to high speed.

When the actual value drops below 63 %, the fans reduce to intermediate speed.
When the actual value drops below 60 %, the fans reduce to low speed and run until dehumidification stops.

140 Test run interval.

Process fan test run interval at fan stop.

141 Test time.

Process fan test run time at fan stop.