6.3.4 Standby / Emergency mode

In the event of an A alarm, which normally stops the dehumidifier, and Reserve operation activated in parameter 480, the dehumidifier continues in the set operating mode as below.

Indicated by the display of “Standby” at the top of the control panel.

Pro:

  • Rotor = Off.
  • Internal electric battery = Off.
  • Process air fan = On.
  • Rain air fan = Off.

Reg:

  • Rotor = Off.
  • Internal electric battery = Off.
  • Process air fan = Off.
  • Rain air fan = On.

Pro + Reg:

  • Rotor = Off.
  • Internal electric battery = Off.
  • Process air fan = On.
  • Rain air fan = On.

To acknowledge standby operation, the alarm must be corrected and acknowledged and the unit must be stopped before it is started again.