EvoControl Ventilation - MPO1 Display
Models: A30T, A50CS, A60T, A70T
Rotating heat exchanger.
The heat exchanger is pulse-controlled for control signals below 100%, i.e. it runs for a number of seconds and then stops for a while depending on the size of the control signal. The heat exchanger is switched off with a delay of 20 minutes if the outdoor temperature is colder than 5°C, at warmer outdoor temperatures the heat exchanger is switched off with a delay of 5 minutes after reheating is not required.
Reservation for errors or linguistic discrepancies that may have arisen during printing, translation or assisted text processing. In case of discrepancies between language versions, the original Swedish version applies. See conditions.