EvoControl Ventilation - MPO1 Display

Models: A30T, A50CS, A60T, A70T

6.8 Heat recovery

Rotating heat exchanger.

The heat exchanger is pulse-controlled for control signals below 100%, i.e. it runs for a number of seconds and then stops for a while depending on the size of the control signal. The heat exchanger is switched off with a delay of 20 minutes if the outdoor temperature is colder than 5°C, at warmer outdoor temperatures the heat exchanger is switched off with a delay of 5 minutes after reheating is not required.