EvoControl Ventilation - MPO1 Display

Models: Modeller syns här inom kort.

7.1.4 Features

400 ECO mode

  • Activation of the function.
  • The heat recovery rotor (VVX) setpoint is equal to the set temperature setpoint in the current operating mode and the reheat gets a new temperature setpoint according to parameter 401.
  • The temperature setpoint of the reheat can never be higher than the temperature setpoint of the heat recovery.
  • The function is then switched on in Menu 1 (Operation).

401 Setpoint ECO

  • Fixed setpoint for reheat.

420 Fire function

  • The function is activated when the end between terminals 9 and 10 is broken.

Selectable in four modes:

  1. Supply air fan stops, extract air fan stops. Damper closes. Heating* and cooling outputs off.
  2. Supply air fan stops, extract air fan 100 per cent. Dampers open. Heating* and cooling outputs off.
  3. Supply air fan 100 per cent, extract air fan stop. Damper opens. Heating* and cooling outputs off.
  4. Supply air fan 100 per cent, extract air fan 100 per cent. Dampers open. Heating* and cooling outputs off.

*Heat output 100 per cent with water coil.

435 Refrigeration recovery

  • Activation of the function.

436 Refrigeration recovery difftemp

  • The rotary heat exchanger starts when the extract air temperature is lower than the outdoor air temperature - set value in the parameter and cooling signal exceeds 10 per cent.

440 Free cooling via outside air

  • Activation of the function.
  • The function means that when the conditions of parameters 441 and 442 are fulfilled, the supply air gets a new setpoint equal to the minimum limitation according to parameter 262.

441 Free cooling at outdoor air temperature

  • Free cooling allowed at outdoor temperature higher than set value.

442 Free cooling at exhaust air temperature

  • Free cooling start temperature when the extract air temperature exceeds the set value.

450 Defrosting

  • Activation of the function.
  • The unit defrosts during defrost time parameter 452 at regular defrost intervals parameter 453 if the outdoor air temperature is lower than the set value parameter 451.
  • The function means that the supply air fan runs in 20% and the heat exchanger (rotor) runs on 78% control signal and that the exhaust air fan runs in at least 50% and any preheating is on.

451 Defrosting start at Utetemp

  • Defrosting Start at outside temperature.

452 Defrosting time

  • Defrosting time in minutes.

453 Defrosting interval

  • Defrosting interval in minutes.

454 VVX Control

Activation of the function. The function means that if the heat exchanger (rotor) stops, 3 attempts are made to start it again before the alarm goes off.

At plus degrees, the control signal to the heat exchanger and the supply air fan becomes 0 for 2 minutes, the extract air fan continues after the set value.
Then the heat exchanger is tested for 1 minute, if the heat exchanger starts signalling again, the unit returns to normal operation.

If it is below freezing outside, it is assumed that the heat exchanger has frozen. Då blir styrsignal till värmeväxlaren och tilluftsfläkten 0 under 10 minuter, frånluftsfläkten går med minst 50%. Then the heat exchanger is tested for 1 minute, if the heat exchanger starts signalling again, a 30-minute defrost is performed before the unit returns to normal operation.

455 Winterisation

  • Activation of the function.
  • Winter operation means that at a certain outdoor temperature, the capacity of the fans is adjusted and the moisture recovery of the rotor is reduced.
  • When the outdoor air temperature is lower than the set start temperature, fan adjustment starts and has full adjustment at 10°C lower temperature than the start temperature.
  • Moisture reduction rotor means that the rotor recovers less moisture and problems with condensation on windows and other cold surfaces are reduced, however the efficiency is slightly reduced.

456 Winter operation Start temperature

  • Winter operation starts at outdoor temperatures lower than the set value.

457 Winter operation Fan Supply air

  • Max fan adjustment supply air.

458 Winter operation Fan Exhaust air

  • Max fan adjustment exhaust air.

459 Winter operation Moisture reduction Rotor

  • Adjusts the rotor moisture recovery.
  • For moisture reduction the appropriate value is 60%.

465 Presence, switch-off delay

  • Activation of the function.
  • When the presence detector (accessory) detects presence on the relevant external input, the unit changes to that operating mode.
  • Returns time set operating mode after set time.
  • Can be overridden with panel and other external inputs to a higher operating mode.

466 Attendance, Operating mode

  • Minimum operating mode when presence is detected.

467 Attendance, Operating Mode Return

  • Return to operating mode after presence not recorded.

470-472 Prioritisation

Operating mode:

  • Fire function, terminals 9 & 10 open.
  • Stop, terminal 7 & 8 open.
  • Forced, terminals 1 & 4 closed.
  • Comfort, terminal 1 & 3 closed.
  • Spar, terminal 1 & 2 closed.
  • Display.

If the priority order, parameter 470-472, is set to “Priority”, the order as above applies if more inputs are active.

If the priority order, parameters 470-472, is set to “Last input”, the last command is valid until the next command.

If parameter 470 is “Prio”, parameters 471-472 are automatically set to “Prio” as well and become hidden in the control panel.

  • A70T with cooker hood 251, “Last input” should be selected.
  • A70T with cooker hood 392 “Prio” should be selected.
  • A70T with Monolit cooker hood “Prio” should be selected.

475 Engine type

  • Induction motor.
  • Stepper motor.
  • Stegmotor RS Nema17.
  • Stegmotor RS Nema24.

476 Stepper motor RS Max speed

The maximum speed of the engine.

480 Standby / Emergency

Back-up operation:

  • Supply air fan = Off.
  • Exhaust air fan = On (capacity according to factory settings in each operating mode in %).
  • Rotor = On.
  • Internal electric battery = Off.
  • For water coil = Normal regulation.

482 Exercise driving

  • Exercise run of rotor. Rotor runs 1 minute at 12:00 and 24:00 if the rotor has been stationary for more than 3 hours.
Subject to typographical errors, translation errors and AI-generated linguistic discrepancies. In case of discrepancies between language versions, the original Swedish version applies.