EvoControl Ventilation Touch Display

Models: A100 G3, A110T G3-G4, A170T G2, A200S, A230T, A250S, A390T, A400S, A590T, A600S/T, A900ST G3, A1, A2, M1, M2, R20, R25, R40, R50, R70

6.2 Start-up / Start-up sequence

When an operating mode is selected in the ventilation unit, the extract fan and the heat exchanger start first.
Depending on the outdoor temperature and the settings of parameters 410 and 411, the supply air fan has a start delay of at least 30 seconds.

The start-up may last longer than the set values:

  • When control is waiting for signals from fans, it can take up to 10 minutes.
  • When control is waiting for signals from the heat exchanger, see Description - Heat recovery.

*Check the “Measured values” menu and the “Extra operating mode” parameter for details.