6.7 External inputs

The capacity and heat of the unit can be changed via potential-free contacts on the terminal block inputs. E.g. occupancy sensor, timer.

The External 1 and External 2 operating modes can only be selected by closing the terminal block and by timer.

Termination on the terminals for Economy, Comfort and Forced corresponds to the same operating mode as when changing on the display.

Operating mode:

  • Fire function, terminals 9 & 10 open.
  • Display operating mode Stop.
  • Stop, terminal 7 & 8 open.
  • External 2, terminal 1 & 6 closed.
  • External 1, terminal 1 & 5 closed.
  • Forced, terminals 1 & 4 closed.
  • Comfort, terminal 1 & 3 closed.
  • Spar, terminal 1 & 2 closed.
  • Display.
  • If the priority order, parameter 470-472, is set to “Priority”, the order as above applies if more inputs are active.
  • If the priority order, parameters 470-472, is set to “Last input”, the last command is valid until the next command.

If parameter 470 is “Prio”, parameters 471-472 are automatically set to “Prio” as well and become hidden in the control panel.

  • A70T with cooker hood 251, “Last input” should be selected.
  • A70T with cooker hood 392 “Prio” should be selected.
  • A70T with Monolit cooker hood “Prio” should be selected.