AVC-02 Ventilation
Models: A50S G1, A70T G1–G2, A100S G1–G2, A110T G1–G2, A200S G1, A170T G1, A900ST G1
| Id | Text | Min | Max | Factory value | Unit |
|---|---|---|---|---|---|
| Programming mode 1 | |||||
| 1 | Programme version control panel | ||||
| 2 | Programme version motherboard in the unit | ||||
| 7 | Receipt alarm | OF | On | OF | |
| 11 | Supply air fan speed ”Economy” | 20 | 80 | 30 | % |
| 12 | Exhaust air fan speed ”Spar” | 20 | 80 | 40 | % |
| 14 | Supply air fan speed ”Comfort” | 30 | 99 | 45 | % |
| 15 | Exhaust air fan speed ”Comfort” | 30 | 99 | 60 | % |
| 17 | Supply air fan speed ”Forced” | 60 | 99 | 60 | % |
| 18 | Fan speed exhaust air ”Forced” | 60 | 99 | 80 | % |
| 21 | Setting the temperature | 12 | 30 | 20 | °C |
| 23 | Activation of temp reduction in ”Save” | OF | On | OF | |
| 25 | Choice of principle for temperature control | tL | FL | tL | |
| 31 | Post-heating battery activated | OF | On | On | |
| 41 | Cooling forcing | OF | On | OF | |
| 43 | Refrigeration recovery | OF | On | OF | |
| 45 | Free cooling via outside air | OF | On | OF | |
| 47 | Defrost function, number of hours between each defrost, of = Defrosting disabled |
OF | 12 | 4 | h |
| 48 | Defrost function, outside temperature below freezing during defrosting activated |
-5 | -25 | -10 | °C |
| 51 | External control 1 fan speed supply air | 20 | 99 | 50 | % |
| 52 | External control 1 fan speed exhaust air | 20 | 99 | 50 | % |
| 53 | External control 1 temperature | 12 | 30 | 20 | °C |
| 55 | External control 2 fan speed supply air | 20 | 99 | 50 | % |
| 56 | External control 2 fan speed exhaust air | 20 | 99 | 50 | % |
| 57 | External control 2 temperature | 12 | 30 | 20 | °C |
| 70 | Moisture reduction | OF | 2 | OF | |
| 71 | Moisture reduction, aggressiveness | 1 | 6 | 6 | |
| 72 | Humidity reduction switch-on temperature | -1 | -25 | -10 | °C |
| 81 | Service alarm 0F=Service alarm disabled, 1–24 months between service alarm |
OF/1 | 24 | OF | m |
| Programming mode 2 | |||||
| 5 | Control units, 1 = Control panel 2 = Modbus 3 = Modbus & Control panel |
1 | 3 | 1 | |
| 9 | Supply air upper fan = 1 Supply air lower fan = 2 | 1 | 2 | 1 | |
| 91 | Fan monitoring, 390T, A400S, A600S/T, A900 S/T = 2. Other units = 1 |
1 | 2 | 1 or 2 | |
| 92 | Priority order: A70T with cooker hood 251 = 3. A70T with cooker hood 392 = 1, all other units = 1 |
1 | 3 | 1 or 3 | |
| 93 | Max limitation of supply air fan | 50 | 99 | 99 | % |
| 94 | Turn-off delay rotary heat exchanger | 0 | 99 | 20 | m |
| 95 | Emergency, Exhaust air operation in case of A-alarm | On | OF | On | |
| 99 | Test mode | On | OF | OF | |
The minimum, maximum and default values of the parameters may vary slightly depending on the programme version!
Reservation for errors or linguistic discrepancies that may have arisen during printing, translation or assisted text processing. In case of discrepancies between language versions, the original Swedish version applies. See conditions.