AVC-02 Ventilation

Models: A50S G1, A70T G1–G2, A100S G1–G2, A110T G1–G2, A200S G1, A170T G1, A900ST G1

5.2 Parameter list

Parameter list
Id Text Min Max Factory value Unit
Programming mode 1
1 Programme version control panel
2 Programme version motherboard in the unit
7 Receipt alarm OF On OF
11 Supply air fan speed ”Economy” 20 80 30 %
12 Exhaust air fan speed ”Spar” 20 80 40 %
14 Supply air fan speed ”Comfort” 30 99 45 %
15 Exhaust air fan speed ”Comfort” 30 99 60 %
17 Supply air fan speed ”Forced” 60 99 60 %
18 Fan speed exhaust air ”Forced” 60 99 80 %
21 Setting the temperature 12 30 20 °C
23 Activation of temp reduction in ”Save” OF On OF
25 Choice of principle for temperature control tL FL tL
31 Post-heating battery activated OF On On
41 Cooling forcing OF On OF
43 Refrigeration recovery OF On OF
45 Free cooling via outside air OF On OF
47 Defrost function, number of hours between each defrost, of =
Defrosting disabled
OF 12 4 h
48 Defrost function, outside temperature below freezing during defrosting
activated
-5 -25 -10 °C
51 External control 1 fan speed supply air 20 99 50 %
52 External control 1 fan speed exhaust air 20 99 50 %
53 External control 1 temperature 12 30 20 °C
55 External control 2 fan speed supply air 20 99 50 %
56 External control 2 fan speed exhaust air 20 99 50 %
57 External control 2 temperature 12 30 20 °C
70 Moisture reduction OF 2 OF
71 Moisture reduction, aggressiveness 1 6 6
72 Humidity reduction switch-on temperature -1 -25 -10 °C
81 Service alarm 0F=Service alarm disabled, 1–24 months between
service alarm
OF/1 24 OF m
Programming mode 2
5 Control units, 1 = Control panel 2 = Modbus 3 = Modbus &
Control panel
1 3 1
9 Supply air upper fan = 1 Supply air lower fan = 2 1 2 1
91 Fan monitoring, 390T, A400S, A600S/T, A900 S/T = 2. Other units
= 1
1 2 1 or 2
92 Priority order: A70T with cooker hood 251 = 3. A70T with cooker hood 392 = 1,
all other units = 1
1 3 1 or 3
93 Max limitation of supply air fan 50 99 99 %
94 Turn-off delay rotary heat exchanger 0 99 20 m
95 Emergency, Exhaust air operation in case of A-alarm On OF On
99 Test mode On OF OF

The minimum, maximum and default values of the parameters may vary slightly depending on the programme version!

Reservation for errors or linguistic discrepancies that may have arisen during printing, translation or assisted text processing. In case of discrepancies between language versions, the original Swedish version applies. See conditions.