Go to content

EvoControl EvoDry RD

Models: EvoDry RD EC

7.1.2 Moisture

200 Humidity control mode

Constant dehumidification, relative humidity, relative humidity and temperature, absolute humidity, dew point or active dew point.

Activation of the active dew point requires a dew point sensor (accessory) and activation of parameter 330.

210 - 213 Exchange values

Setpoint after humidity control mode.

220 Start hysteresis in %

Start hysteresis for when to start dehumidification.

Applies to humidity control mode relative humidity, relative humidity and temperature, absolute humidity.

221 Stop hysteresis in %

Start hysteresis for when to start dehumidification.

Ex.
Setpoint = 60 % , start hysteresis = 2% and stop hysteresis = -4%
Dehumidification starts at 62% and stops at 56%

223 Start hysteresis in °K

Start hysteresis for when to start dehumidification.

Applies to humidity control mode dew point and active dew point control.

224 Stop hysteresis in °K

Start hysteresis for when to start dehumidification.

Reservation for errors or linguistic discrepancies that may have arisen during printing, translation or assisted text processing. In case of discrepancies between language versions, the original Swedish version applies. See conditions.

© 2026 Acetec AB. All rights reserved.