7.1.2 Moisture
200 Humidity control mode
Constant dehumidification, relative humidity, relative humidity and temperature, absolute humidity, dew point or active dew point.
Activation of the active dew point requires a dew point sensor (accessory) and activation of parameter 330.
210 - 213 Exchange values
Setpoint after humidity control mode.
220 Start hysteresis in %
Start hysteresis for when to start dehumidification.
Applies to humidity control mode relative humidity, relative humidity and temperature, absolute humidity.
221 Stop hysteresis in %
Start hysteresis for when to start dehumidification.
Ex.
Setpoint = 60 % , start hysteresis = 2% and stop hysteresis = -4%
Dehumidification starts at 62% and stops at 56%
223 Start hysteresis in °K
Start hysteresis for when to start dehumidification.
Applies to humidity control mode dew point and active dew point control.
224 Stop hysteresis in °K
Start hysteresis for when to start dehumidification.