2.4 Humidity setting

Constantly on.

Dehumidification is constantly taking place.

RF.

Dehumidification starts when the relative humidity of the air exceeds the set value.

RF + Temp.

Dehumidification starts when the relative humidity of the air exceeds the set value at temperatures above +15°C.
The moisture content is allowed to rise by 1%/°C at temperatures below +15°C before dehumidification starts.
The function is only active in the temperature range 0-15°C.

AF.

Dehumidification starts when the absolute humidity in the air exceeds the set value.

Dew point.

Dehumidification starts when the dew point in the air exceeds the set value.

Active dP.

Dehumidification begins when the dew point in the air exceeds the temperature of the surface temperature sensor plus the setpoint.
A surface temperature sensor is required (accessory).