EvoControl EvoDry RD

Models: EvoDry RD EC

6.3.1 Function

If the alarm is active or unacknowledged, the alarm symbol appears at the top of the display and the alarm is added to the alarm list.

A-alarm

  • The dehumidifier is stopped *1.
  • Manual acknowledgement of alarms is required, and faults must be cleared before restart *2.

**1 If Standby mode, parameter 480, is enabled (see function in the parameter list).

**2 To exit Standby mode, the fault must be cleared and acknowledged, then the unit must be Stopped before restarting.

B-alarm

  • The dehumidifier continues to run.
  • Manual acknowledgement of alarms

C-alarm

  • The dehumidifier continues to run.
  • Automatic acknowledgement when alarm returns to normal or manual acknowledgement of alarm.